OMRON 3G3MX2 Inverter Models

OMRON 3G3MX2 Inverter Models

Price:
0.00
Detail

Model name

Rated input voltage

Enclosure ratings

Max. applicable motor capacity

CT: Heavy load

VT: Light load

3G3MX2-A2001-ZV1

3-phase
AC200V

IP20

0.1kW

0.2kW

3G3MX2-A2002-ZV1

0.2kW

0.4kW

3G3MX2-A2004-ZV1

0.4kW

0.75kW

3G3MX2-A2007-ZV1

0.75kW

1.1kW

3G3MX2-A2015-ZV1

1.5kW

2.2kW

3G3MX2-A2022-ZV1

2.2kW

3.0kW

3G3MX2-A2037-ZV1

3.7kW

5.5kW

3G3MX2-A2055-ZV1

5.5kW

7.5kW

3G3MX2-A2075-ZV1

7.5kW

11kW

3G3MX2-A2110-ZV1

11kW

15kW

3G3MX2-A2150-ZV1

15kW

18.5kW

3G3MX2-A4004-ZV1

3-phase
AC400V

IP20

0.4kW

0.75kW

3G3MX2-A4007-ZV1

0.75kW

1.5kW

3G3MX2-A4015-ZV1

1.5kW

2.2kW

3G3MX2-A4022-ZV1

2.2kW

3.0kW

3G3MX2-A4030-ZV1

3.0kW

4.0kW

3G3MX2-A4040-ZV1

4.0kW

5.5kW

3G3MX2-A4055-ZV1

5.5kW

7.5kW

3G3MX2-A4075-ZV1

7.5kW

11kW

3G3MX2-A4110-ZV1

11kW

15kW

3G3MX2-A4150-ZV1

15kW

18.5kW

3G3MX2-AB001-ZV1

1-phase
AC200V

IP20

0.1kW

0.2kW

3G3MX2-AB002-ZV1

0.2kW

0.4kW

3G3MX2-AB004-ZV1

0.4kW

0.55kW

3G3MX2-AB007-ZV1

0.75kW

1.1kW

3G3MX2-AB015-ZV1

1.5kW

2.2kW

3G3MX2-AB022-ZV1

2.2kW

3.0kW

Function name

Specifications

Enclosure ratings

Open type (IP20)

Control method

Phase-to-phase sinusoidal modulation PWM

Output frequency range

0.10 to 400 Hz (or 580 Hz in the high-frequency mode; restrictions apply)

Frequency precision

Digital command: ±0.01% of the max. frequency, Analog command: ±0.2% of the max. frequency (25±10°C

Frequency setting resolution

Digital setting: 0.01 Hz, Analog setting: One-thousandth of the maximum frequency

Voltage/Frequency characteristics

V/f characteristics (constant/reduced torque) Sensorless vector control, V/f control with speed feedback

Overload current rating

Heavy load rating (CT): 150%/60 s

Light load rating (VT): 120%/60 s

Instantaneous overcurrent protection

200% of the value of heavy load rating (CT)

Acceleration/Deceleration time

e 0.01 to 3600 s (linear/curve selection), acceleration/deceleration 2 setting available

Carrier frequency adjustment range

2 to 15 kHz (with derating)

Starting torque

200%/0.5 Hz (sensorless vector control)

External DC injection braking

Starts at a frequency lower than that in deceleration via the STOP command, at a value set lower than that during operation, or via an external input. (Level and time settable).

Protective functions

Overcurrent, overvoltage, undervoltage, electronic thermal, temperature error, ground fault overcurrent at power-on status, rush current prevention circuit, overload limit, incoming overvoltage, external trip, memory error, CPU error, USP error, communication error, overvoltage suppression during deceleration, protection upon momentary power outage, emergency cutoff, etc.

Frequency settings

Digital Operator External analog input signal: 0 to 10 VDC/4 to 20 mA, Modbus communication (Modbus-RTU)

RUN/STOP command

Digital Operator External digital input signal (3-wire input supported), Modbus communication (Modbus-RTU)

Multi-function input

7 points (Selectable from 59 functions

Analog input

2 points (Voltage FV terminal: 10 bits/0 to 10 V, Current FI terminal: 10 bits/4 to 20 mA)

Pulse input

1 point (RP terminal: 32 kHz max., 5 to 24 VDC)

Multi-function output

2 points (P1/EDM, P2; selectable from 43 functions)

Relay output

1 point (1c contact: MC, MA, MB; selectable from 43 functions)

Analog output (Frequency monitor)

1 point (AM terminal: Voltage 10 bits/0 to 10 V) (Frequency, current selectable)

Pulse input

1 point (RP terminal: 32 kHz max., 5 to 24 VDC)

Drive Programming

Calculate, Logic, Control I/O and so on

Ambient operating temperature

-10 to 50°C (However, derating is required)

Ambient storage temperature

-20°C to 65°C

Ambient operating humidity

20% to 90% RH (with no condensation)

Vibration resistance

5.9 m/s2 (0.6G), 10 to 55 Hz

Application environment

At a maximum altitude of 1,000 m; indoors (without corrosive gases or dust)

Other option

DC reactor, AC reactor, radio noise filter, input noise filter, output noise filter, regenerative braking unit, Braking Resistor, etc.

*